In this study, the cooling performance of the multi-split variable refrigerant flow (VRF) air conditioning system operated in the academic building environment was simulated with EnergyPlus software, which has a new module for VRF heat pump systems. Simulation results were validated with the field test results during the cooling season. The comparison result shows that 87.5% of all simulated daily power consumption data agree with the experimental data within ±15% deviation. The root-mean-square deviations of daily, weekly and monthly electricity power consumptions for the total simulation period between the simulated and measured values are 5.63 kWh, 11.12 kWh and 37.58 kWh, respectively. The averages of the absolute values of the daily, weekly and monthly relative error for the total simulation period are 7.97%, 2.40% and 2.22%, respectively.
机译:在这项研究中,使用EnergyPlus软件模拟了在学术建筑环境中运行的多分裂可变制冷剂流量(VRF)空调系统的冷却性能,该软件具有一个用于VRF热泵系统的新模块。冷却季节期间,通过现场测试结果验证了仿真结果。比较结果表明,所有模拟的每日耗电量数据中的87.5%与实验数据相符,误差在±15%之内。在整个模拟期间,模拟,测量值之间的每日,每周和每月电力消耗的均方根偏差分别为5.63 kWh,11.12 kWh和37.58 kWh。在整个模拟期间内,每日,每周和每月相对误差的绝对值的平均值分别为7.97%,2.40%和2.22%。