首页> 外文会议>IEEE International Conference on Smart Grid Communications >On-line oscillations monitoring under high penetration of non-synchronous generation
【24h】

On-line oscillations monitoring under high penetration of non-synchronous generation

机译:在非同步发电的高渗透下在线振荡监测

获取原文

摘要

The large scale penetration of non-synchronous generation based power electronics converters interfaces in current power systems is modifying their dynamic characteristics. The observation, monitoring and supervision of the electromechanical oscillation changes due to this integration is a requirement in order to protect the system from undesired events. This paper uses the Prony analysis to estimate the critical modes by using the tie-lines which interconnect the operative areas as measurement points and evaluating the impact of the large gradual scale inclusion of non-synchronous generation on power systems. The modes monitoring involved in the transient dynamic response are shown in the different penetration level cases. From the computed measurements, the frequency and damping variation in the different cases studied on the test system is obtained, which shows the impact of the large inclusion of non-synchronous generation.
机译:基于非同步产生的基于功率电子转换器的大规模渗透在当前电力系统中的接口正在修改其动态特性。由于这种集成而导致的机电振荡变化的观察,监测和监督是一种要求,以便保护系统免受不期望的事件。本文采用PRONY分析通过使用将操作区域互连为测量点的连接线来估计临界模式,并评估大逐渐扩展的非同步发电对电力系统的影响。瞬态动态响应所涉及的模式监测在不同的穿透级别情况下显示。从计算的测量中,获得了在测试系统上研究的不同案例中的频率和阻尼变化,其显示了大包含非同步产生的影响。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号