Field Survey on Indoor Thermal Environment in Small to Medium Sized Building with Packaged Air Conditioners

机译:中小型成套空调室内热环境实地调查

获取原文

摘要

Recently, a lot of multiple packaged unit system is adopted in small to medium sized buildings in Japan. This system enables to control each packaged air conditioner (PAC) individually because multiple packaged units are placed decentrally. However, it is not clarified sufficiently how indoor environment is formed when PAC is working. This paper shows the measurement results of indoor thermal environment in a medium sized building with PAC in all season for the purpose of clarifying the current status of indoor environment and its issue. In indoor thermal environment, there was no issue throughout the year though measurement conditions made difference in temperature and humidity distribution. In indoor units operation, it was clarified that supply air temperature of PAC is different from each PAC and way. In addition, it was clarified that short circuit of supply air from PAC to inlet of the ventilation devices happen.
机译:近来,在日本的中小型建筑物中采用了许多多包装单元系统。由于多个包装单元分散放置,因此该系统可以分别控制每个包装的空调(PAC)。但是,PAC工作时如何形成室内环境还不够清楚。为了阐明室内环境的现状及其存在的问题,本文显示了一个带有PAC的中型建筑在整个季节中对室内热环境的测量结果。在室内热环境中,尽管测量条件使温度和湿度分布有所不同,但全年没有任何问题。在室内机操作中,已弄清楚PAC的送风温度与每个PAC和方式不同。另外,已经澄清了从PAC到通风设备的入口的供应空气的短路发生。