摘要

It is important to evaluate the validity and safety of the substation earthing system since over time the physical and electrical properties or requirements of the substation earthing can change in many ways. A research study focused on safety assessment of substation earthing systems due to variations of soil resistivities values which dependent on tropical rainfall variations was carried out on a 132kV substation. Actual earthing resistances and soil resistivities values were measured at a regular interval for a period of 18-months as input to the simulation process. The study used CDEGS™ software for modeling and assessment of substations earthing system safety. From the initial desktop simulation calculation based on the above models, it was found that the substation have its touch and step voltages exceeded the allowable limits as per IEEE 80–2000 Standard (IEEE Guide for Safety in AC Substation Grounding) for some period throughout the duration of the study.
机译:评估变电站接地系统的有效性和安全性很重要,因为随着时间的流逝,变电站接地的物理和电气特性或要求可能会发生多种变化。在132kV变电站上进行了一项针对土壤变电阻率值变化的研究,该变电站接地系统由于土壤电阻率值的变化而变化,而土壤电阻率值的变化取决于热带降雨的变化。在为期18个月的定期时间内,测量了实际的接地电阻和土壤电阻率值,作为模拟过程的输入。该研究使用CDEGS™软件对变电站接地系统的安全性进行建模和评估。从基于上述模型的初始桌面模拟计算中,发现变电站在整个运行过程中的一段时间内,其接触电压和步进电压均超过了IEEE 80–2000标准(IEEE交流变电站接地安全指南)的允许极限。研究的持续时间。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号