首页> 外文会议>2011 4th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies >Single phase to earth fault location method in distribution network based on signal injection principle
【24h】

Single phase to earth fault location method in distribution network based on signal injection principle

机译:基于信号注入原理的配电网单相接地故障定位方法

获取原文

摘要

A single phase to earth fault location method in distribution network based on signal injection principle is proposed. It is expected to solve single phase to earth fault location problem in neutral indirectly earth system. When single phase to earth fault occurs, a sine current signal with constant frequency is injected into the fault phase from potential transformer's secondary side, the injected signal current and its voltage drop on the fault line can be measured through the fault line's zero sequence current transformer (CT) and potential transformer (PT) on the bus. Based on distributed parameter model of distribution line, we can get the relational expressions between injected signal voltage and current at measuring point and fault point, then, we can solve the fault distance by using the resistive characteristic of transition resistance. This method is not affected by system structure and operating mode, and the use of distributed parameter line model eliminating the impact of distributed capacitance, the result of fault distance has high precision. Simulation results verify the correctness and feasibility of the proposed method.
机译:提出了一种基于信号注入原理的配电网单相接地故障定位方法。有望解决中性间接接地系统中单相接地故障的定位问题。当发生单相接地故障时,将恒定频率的正弦电流信号从电压互感器的次级侧注入故障相,可以通过故障线的零序电流互感器来测量注入的信号电流及其在故障线上的压降。 (CT)和电位互感器(PT)放在总线上。基于配电线路的分布参数模型,可以得到注入点电压和电流在测量点和故障点的关系式,然后利用过渡电阻的电阻特性来求解故障距离。该方法不受系统结构和工作方式的影响,采用分布参数线模型消除了分布电容的影响,故障距离的结果具有较高的精度。仿真结果验证了该方法的正确性和可行性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号