Application and positioning analysis of a resistive type Superconducting Fault Current Limiter in AC and DC microgrids using Simulink and SimPowerSystem

机译:使用Simulink和SimPowerSystem的电阻型超导故障限流器在交直流微电网中的应用和定位分析

获取原文

摘要

Conventional protection devices installed for the protection of excessive fault current in the electric power system have a certain response time delay resulting in power system to pass initial peaks of fault current. Superconducting Fault Current Limiter (SFCL) is a novel technology which has negligible power loss and capability to quench initial fault currents instantly and it also could be utilized to cope with excessive fault current problems in upcoming microgrids. This paper presents feasibility analysis results of positioning of the SFCL and its effects on reducing fault current in microgrids. The detailed power system having AC and low voltage DC microgrids consist of integrated wind and photovoltaic farms integrated with a traditional power system is modeled. Transient analyses for the microgrids were performed for the worst case faults with SFCL installed at key locations of the microgrids. It has been observed that SFCL should not be installed directly at the substation or the branch network feeders. This placement of SFCL results in abnormal fault current contribution from the DG sources. The strategic location of SFCL in power grid which limits all fault currents and has no negative effect on the DG sources is found to be in front of the point of integration of the DG sources with the microgrid.
机译:为保护电力系统中过多的故障电流而安装的常规保护装置具有一定的响应时间延迟,从而导致电力系统通过故障电流的初始峰值。超导故障电流限制器(SFCL)是一项新颖的技术,其功率损耗可忽略不计,能够立即消除初始故障电流,并且还可以用来应对即将到来的微电网中过多的故障电流问题。本文介绍了SFCL定位的可行性分析结果及其对减少微电网故障电流的影响。具有交流和低压直流微电网的详细电力系统由集成的风力发电场和光伏发电场组成,并与传统电力系统进行了建模。对于微电网的瞬态分析是在微电网的关键位置安装了SFCL来进行最坏情况的故障分析。已经观察到,SFCL不应直接安装在变电站或分支网络馈线中。 SFCL的这种放置会导致DG源产生异常故障电流。发现SFCL在电网中的战略位置位于限制所有故障电流且对DG源没有负面影响的位置,位于DG源与微电网的集成点之前。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号