首页> 外文会议>2011 1st International Conference on Electric Power Equipment - Switching Technology >Calculation and verification of current limiting properties for Saturated Iron Core Superconductive Fault Current Limiter
【24h】

Calculation and verification of current limiting properties for Saturated Iron Core Superconductive Fault Current Limiter

机译:饱和铁芯超导故障限流器限流特性的计算与验证

获取原文

摘要

This paper introduces a simulation model of Saturated Iron Core Superconducting Fault Current Limiter (SICSFCL) using SIMPOWER of MATLAB and establishes an actual model for the 35kV/90MVA SICSFCL installed in Puji substation at Kunming. The model is used to simulate the artificially imposed three-phase short-circuit and the results are compared to the live grid test results, which were carried out in July 2009. The SICSFCL simulation model is verified effectively.
机译:本文介绍了使用MATLAB的SIMPOWER建立的饱和铁芯超导故障电流限制器(SICSFCL)的仿真模型,并为安装在昆明普济变电站内的35kV / 90MVA SICSFCL建立了一个实际模型。该模型用于仿真人为施加的三相短路,并将结果与​​2009年7月进行的带电电网测试结果进行比较。SICSFCL仿真模型得到了有效验证。