首页> 外文会议>IFIP TC 12 conference on computer and computing technologies in agriculture;CCTA 2010 >Simulation Study of Single Line-to-Ground Faults on Rural Teed Distribution Lines
【24h】

Simulation Study of Single Line-to-Ground Faults on Rural Teed Distribution Lines

机译:农村三通配电线路单线接地故障的仿真研究

获取原文

摘要

Teed lines are widely used in rural power networks in China. The paper theoretically analyzes the voltages and currents when a single line-to-ground fault occurs, constructs a new mathematical model for fault location on the teed lines, performs corresponding MATLAB simulations. Simulation results show that currents near the source (bus M) are almost independent of fault positions and fault resistances. However, voltages at bus M are sensitive to fault positions while fault voltages at fault position are only sensitive to transient resistances. A novel approach to fault location on teed lines is proposed. First, the faulted line is identified with remote control equipment. Then, the transient resistances are calculated according to the fault voltages. And at last, the fault distances are computed according to the voltages at bus M and the calculated transient resistances.
机译:三通线路在中国的农村电网中得到了广泛的应用。本文从理论上分析了发生单线接地故障时的电压和电流,构建了三端在线故障定位的新数学模型,并进行了相应的MATLAB仿真。仿真结果表明,电源(母线M)附近的电流几乎与故障位置和故障电阻无关。但是,母线M上的电压对故障位置敏感,而故障位置上的故障电压仅对瞬态电阻敏感。提出了一种新的方法来处理在线线路上的故障。首先,用远程控制设备识别故障线路。然后,根据故障电压计算瞬态电阻。最后,根据母线M处的电压和计算出的瞬态电阻来计算故障距离。