首页> 外文会议>45th International Universities Power Engineering Conference (UPEC) >The neutral grounding resistor sizing using an analytical method based on nonlinear transformer model for inrush current mitigation
【24h】

The neutral grounding resistor sizing using an analytical method based on nonlinear transformer model for inrush current mitigation

机译:基于非线性变压器模型的解析方法确定中性点接地电阻的大小,以减轻浪涌电流

获取原文

摘要

It was found that a neutral resistor together with ‘simultaneous’ switching didn''t have any effect on either the magnitudes or the time constant of inrush currents. The pre-insertion resistors were recommended as the most effective means of controlling inrush currents. Through simulations, it was found that the neutral resistor had little effect on reducing the inrush current peak or even the rate of decay as compared to the cases without a neutral resistor. The use of neutral impedances was concluded to be ineffective compared to the use of pre-insertion resistors. This finding was explained by the low neutral current value as compared to that of high phase currents during inrush. The inrush currents could be mitigated by using a neutral resistor when sequential switching is implemented.
机译:结果发现,中性电阻与“同时”切换不影响浪涌电流的大小或时间常数。建议使用预插入电阻器作为控制浪涌电流的最有效方法。通过仿真发现,与没有中性电阻的情况相比,中性电阻对减小浪涌电流峰值甚至衰减率几乎没有影响。得出的结论是,与使用预插入电阻器相比,使用中性阻抗是无效的。与浪涌期间的高相电流相比,中性电流值低而解释了这一发现。当实现顺序开关时,可以通过使用中性电阻来减轻浪涌电流。