In order to improve the efficiency of power distribution and for economic reasons, the power factor is corrected on medium voltage electrical network. To do this, it is mandatory to switch once or twice a day a capacitor bank. Vacuum circuit breakers are frequently used to switch capacitor banks. An automated system is used to evaluate the electrical life of vacuum circuit breakers depending on the shunt capacitor switching parameters. Tests consist of opening and closing operations on a three-phase circuit breaker. This system has two main advantages; the maximum reactive power available is 20 Mvar at 24 kV with inrush currents up to 22 kA (common values in customer applications are under 10 kA) and the short endurance test duration is only 8 days for 10,000 operations compared to 5 weeks in laboratories.
机译:为了提高配电效率并出于经济原因,在中压电网上对功率因数进行了校正。为此,必须每天更换一次或两次电容器组。真空断路器通常用于开关电容器组。根据并联电容器的开关参数,使用自动化系统来评估真空断路器的电气寿命。测试包括对三相断路器的分闸和合闸操作。该系统具有两个主要优点;在24 kV时,最大可用无功功率为20 Mvar,浪涌电流高达22 kA(客户应用中的常用值在10 kA以下),并且短寿命测试持续时间仅为10,000次操作为8天,而实验室为5周。