On small current grounding system in single-phase grounding fault line selection based on DSP

机译:基于DSP的小电流接地系统单相接地故障选线

获取原文

摘要

The fault mechanism of small current grounding system in single-phase grounding is discussed, and the principle of fault line selection of transient component on faulty phase current is indicated. By the design of hardware and software, it is proved the amplitudes summation of zero sequence transition current between fault line and healthy lines makes a big difference in the feature band. The analysis of the system simulation shows the area of zero sequence transition current on fault line in the spectrum is the largest. Therefore, the application of small current grounding system in single-phase grounding fault line selection based on DSP is an advanced novel method which can distinguish between fault line and healthy lines effectively and accurately.
机译:讨论了单相接地中小电流接地系统的故障机理,指出了故障相电流上暂态分量的故障选线原理。通过硬件和软件的设计,证明了故障线和健康线之间零序过渡电流的幅值总和在特征带上有很大的差异。系统仿真分析表明,频谱中故障线上零序过渡电流的面积最大。因此,小电流接地系统在基于DSP的单相接地故障选线中的应用是一种能够有效,准确地区分故障线和健康线的先进方法。