首页> 外文会议>14th International Conference on Harmonics and Quality of Power >Harmonic emission before and after changing to LED and CFL — Part II: Field measurements for a hotel
【24h】

Harmonic emission before and after changing to LED and CFL — Part II: Field measurements for a hotel

机译:更换为LED和CFL之前和之后的谐波发射-第二部分:酒店的现场测量

获取原文

摘要

This paper shows the results of measurements performed with a medium-sized hotel in the North of Sweden. The harmonic emission and other parameters were measured before, during and after a replacement of all incandescent lamps with energy saving lamps, both compact fluorescent lamps (CFL's) and light emitting diodes (LED's). it was not possible to see any major difference in harmonic spectrum before and after the replacement. The reduction in power factor that was observed was completely due to the reduction in active power.