This paper presents an investigation after the impact on a number of power-quality parameters due to the change from incandescent lamps to energy saving lamps like CFL and LED. The measurements were conducted in a full-scale laboratory model with ordinary household equipment connected, thus simulating an ordinary domestic customer. Incandescent lamps have been replaced in stages by CFL and LED lamps. The CFL's and LED lamps will contribute to an increase in current distortion but the amplitude of the harmonics is quite low so the change of lighting will only have a minor effect on the total current harmonic distortion. It is also shown that the (total) power factor is not a good indicator to compare the impact of different loads on the system.
机译:从白炽灯到节能灯(如CFL和LED)的变化对许多电能质量参数产生影响之后,本文进行了一项调查。在连接了普通家用设备的全面实验室模型中进行测量,从而模拟了普通家用用户。白炽灯已逐步被CFL和LED灯取代。 CFL和LED灯将导致电流失真的增加,但是谐波的幅度非常低,因此照明的变化只会对总电流谐波失真产生较小的影响。还表明,(总)功率因数不是比较不同负载对系统影响的良好指标。