首页> 外文会议>World conference on timber engineering >Fire Resistance of Steel Column Glued with Structural Glulam Covers
【24h】

Fire Resistance of Steel Column Glued with Structural Glulam Covers

机译:钢柱的耐火性粘在结构胶水覆盖物

获取原文

摘要

Composite material has two options. One option is glued with structural steel and 60mm structural glulam. The other option is composed with structural steel, 15mm gypsum board and 30mm structural glulam. Used glulam(Korean Larch) laminated with Polyurethane resin adhesive between wood and steel . Gypsum board jointed with wood plugs and laminated with resorcinol resin adhesive between structural glulam. Columns tested Fire resistance test based on KS F 2257, ISO 834, ASTM E 119 for one hour and nonloading. Criteria are average temperature has to under 538 °C and maximum temperature should not up to 649 °C. Average temperatures of web and flange on composite material I is not exceed the criterion temperature. Maximum temperature of flange and web on composite material II is also not increase up to the criterion temperature. The results show that composite materials have one hour fire resistance performance.
机译:复合材料有两种选择。一种选项采用结构钢和60mm结构胶素胶合。另一种选择采用结构钢,15mm石膏板和30mm结构胶壳组成。用木材和钢之间的聚氨酯树脂粘合剂层压使用胶猩猩(韩国落叶松)。石膏板与木塞接合并用结构甘油甘油甘油胶之间与间苯二酚树脂粘合剂层压。基于KS F 2257,ISO 834,ASTM E 119的柱子测试耐火测试1小时和不加载。标准是平均温度超过538°C,最高温度应高达649°C。复合材料上的网和法兰的平均温度I不超过标准温度。复合材料II上的法兰和网的最大温度也不会增加标准温度。结果表明,复合材料具有1小时的耐火性能。