首页> 外文会议>International Conference on Building Energy and Environment >COP-restricting Parameter Analysis of Centrifugal Refrigerating Units
【24h】

COP-restricting Parameter Analysis of Centrifugal Refrigerating Units

机译:离心式制冷机组的COP限制参数分析

获取原文

摘要

The method of variance analysis was used to analyze the effects of four parameters,i.e.the opening degree of guide vane,the proportion of actual operating load,the outlet temperature of cold water,and the outdoor wet-bulb temperature,on the coefficient of performance (COP)of centrifugal refrigerating units.When the confidence level is set as 95% and 99%respectively,the results of single-factor variance analysis of the above four parameters show that the test statistic F of the opening degree of guide vane is higher than its critical value F0.01 (r-1,n-r) ,and the F of the proportion of actual operating load and the outlet temperature of cold water are higher than their own critical value F005 (r-1,n-r) ,which proves that their impacts on the COP are significant,while the impact of outdoor wet-bulb temperature is not significant.The results of two-factor variance analysis of the outlet temperature of cold water and outdoor wet-bulb temperature show that their interaction has remarkable impacts on the COP.The actual COP value of centrifugal refrigerating units can increase by 6.885%averagely under the condition of the invariable refrigerating capacity after adjustment according to the analytical results.
机译:采用方差分析的方法分析了导叶的开度,实际工作负荷的比例,冷水出口温度,室外湿球温度这四个参数对性能系数的影响。分别设置置信度为95%和99%时,以上四个参数的单因素方差分析结果表明,导叶开度的测试统计量F较高比其临界值F0.01(r-1,nr)高,并且实际运行负荷与冷水出口温度之比的F高于其自身临界值F005(r-1,nr),这证明冷水出口温度与室外湿球温度的二因素方差分析结果表明,它们之间的相互作用具有显着性。根据分析结果调整后,在制冷量不变的情况下,离心式制冷机组的实际COP值平均可增加6.885%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号