The Co-generation power plants need a cooling Tower to circulate the cold water through the condenser. In a steam power plant about 4800KJ heat is rejected to the circulating water for each KWH of energy produced. Thus by using condenser the exhaust pressure of steam is decreased below atmospheric pressure thus increasing the out put and the efficiency. Thus cooling Tower is one of the important equipment in the power plants. The water used must be treated mainly to prevent corrosion and sale formation in the tube bundle. Also chocking due to Algae formation and bacteria growth in PVC Fill of cooling tower is observed. Clean condenser helps to maintain the vacuum & operate the unit at full efficiency. Proper method of water treatment must be adopted to improve the cooling efficiency and power output. A case study of cooling water related problems & treatment aspects of 6 MW Co-generation Plant of M/s Bhimashankar S S K Ltd., Ambegaon, Pune, is discussed in the foregoing sections.
机译:热电联产电厂需要一个冷却塔,以使冷水通过冷凝器循环。在蒸汽发电厂中,每产生1 KWH的能量,大约4800KJ的热量就会散发到循环水中。因此,通过使用冷凝器,蒸汽的排气压力降低到大气压以下,从而提高了产量和效率。因此,冷却塔是发电厂中的重要设备之一。必须对使用的水进行主要处理,以防止在管束中腐蚀和形成水垢。还观察到由于冷却塔的PVC填料中藻类的形成和细菌的生长而导致堵塞。清洁的冷凝器有助于保持真空并以最高效率运行设备。必须采用适当的水处理方法以提高冷却效率和功率输出。在前面的部分中,讨论了M / s Bhimashankar S S K K.公司(浦那Ambegaon)的6 MW热电厂的冷却水相关问题及处理方面的案例研究。