New Line-selection Method for Single Phase Grounding Fault in Distribution Networks with Two Phase's Current Transformers

机译:两相电流互感器配网单相接地故障的选线新方法

获取原文

摘要

In China,current transformers (TAs) are just installed at A-phase and C-phase in most distribution networks with neutral indirectly grounding.It is a very difficult problem to select single-phase grounding line using the currents of A phase and B phase.After analyzing the currents of A-phase and C-phase when B-phase grounding fault occurs,the fault line detection algorithm applying the transient characters of the sum of A-phase mutational current and C-phase mutational current is proposed.For A-phase to ground fault or C-phase to ground fault,the algorithm of constructing B-phase transient current and furthermore constructing the exact zero-sequence current is founded out through the analysis in frequency domain and time domain,and the fault line-detection method can be actualized according to zero-sequence current's transient characters.Based on them,a new method used to identify single phase to ground fault line using transient characteristics in two TAs distribution networks is formed.The proposed line-selection method is not affected by the mode whether the Petersen coil exists at neutral and the unbalanced current under normal operation condition.
机译:在中国,大多数配电网中都存在中性点间接接地的电流互感器(TA)仅仅安装在A相和C相的情况下,利用A相和B相电流选择单相接地线是一个非常困难的问题。在分析了发生B相接地故障时A相和C相电流之后,提出了一种利用A相突变电流和C相突变电流之和的暂态特性的故障线检测算法。相接地故障或C相接地故障,通过频域和时域分析以及故障线路检测,建立了构造B相暂态电流并构造精确的零序电流的算法。根据零序电流的暂态特性,可以实现该方法。在此基础上,形成了一种利用两个TAs配电网中的暂态特性识别单相接地故障线的新方法。在正常工作条件下,所选择的线路选择方法不受Petersen线圈是否存在于中性点和不平衡电流的模式的影响。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号