首页> 外文会议>42nd internaitonal universities power engineering conference >CURRENT DISTRIBUTION ON TOWER LINES UNDER FAULT AND SURGE CONDITIONS
【24h】

CURRENT DISTRIBUTION ON TOWER LINES UNDER FAULT AND SURGE CONDITIONS

机译:故障和浪涌条件下塔架线路上的电流分布

获取原文

摘要

In this paper, an investigation of current distribution on tower lines under lightning and power frequency fault conditions is carried out. An equivalent circuit model of a 400kV double-circuit transmission line was established using EMTP and two models of differing complexity were developed. The power-frequency earth fault was simulated by short circuiting one phase conductor to the earth wire while lightning conditions were simulated by injecting an impulse-type current onto the earthwire and also onto to one phase conductor. The current and potential distribution through the tower line was examined for different fault locations and the effects of soil resistivity and tower footing resistance variations were quantified.
机译:本文对雷电和工频故障条件下铁塔线路的电流分布进行了研究。利用EMTP建立了400kV双回输电线路的等效电路模型,并开发了两种复杂度不同的模型。工频接地故障是通过将一相导体与接地线短路来模拟的,而雷电条件是通过向接地线以及一相导体上注入脉冲型电流来模拟的。通过塔线的电流和电势分布检查了不同的断层位置,并定量了土壤电阻率和塔基电阻变化的影响。