首页> 外文会议>Power Systems Conference, 2006. MEPCON 2006 >Study of the effect of harmonics on measurments of the energy meters
【24h】

Study of the effect of harmonics on measurments of the energy meters

机译:研究谐波对电表测量的影响

获取原文

摘要

An investigation of the effect of voltage and current harmonics on the accuracy of readings of energy meters was carried out. Harmonic distortion is one of the power quality problems, which typically arises from the consumer''s electrical equipment. Such harmonics produced by discontinuous conducting devices and non-linear loads create recognized problems for most power distribution systems. These problems can lead to over heating and power losses of power system distribution components. Such conditions involved differences in voltage and current magnitudes as well as differences in the voltage and current total harmonic distortion levels. This study presents comparison between the electromechanical energy meters and the electronic digital energy meters. The study also includes the accuracy of readings when the meters are subjected to the same non-linear similar conditions. The harmonics were measured using VIP system III illustrating the THD of voltage and current when power factor compensating capacitors were used or not. It was found that the accuracy and the sensitivity as well as the precision of digital electronic meters are higher than that of the electromechanical one. When using both meters to read the energy consumed by the loads, it was noticed that there is a difference between readings of the two compared types as the digital electronic meter has a difference of (± 0.5% to 1% ) which is a considerable amount of energy for large consumers. An economical assessment was made and showed that the digital meter is saving about L.E 1.8 to 3.6 million per annum for the distribution company. It is recommended to distribution companies to use digital meters instead of electromechanical ones especially for large and medium consumers.
机译:研究了电压和电流谐波对电表读数精度的影响。谐波失真是电能质量问题之一,通常是由用户的电气设备引起的。由不连续的导电设备和非线性负载产生的此类谐波会为大多数配电系统带来公认的问题。这些问题可能导致功率分配系统过热和功率损耗。这些条件包括电压和电流幅度的差异以及电压和电流总谐波失真水平的差异。这项研究提出了机电式电度表和电子数字式电度表之间的比较。该研究还包括当仪表处于相同的非线性相似条件下时的读数准确性。使用VIP系统III测量谐波,该系统说明了无论是否使用功率因数补偿电容器的电压和电流的THD。结果发现,数字电子式电表的精度,灵敏度和精度均高于机电式电表。当使用两个电表读取负载消耗的能量时,注意到两种比较类型的读数之间存在差异,因为数字电子电表的差异为(±0.5%到1%),这是一个相当大的数量大型消费者的能源消耗。进行了一项经济评估,结果表明,数字电表每年为配电公司节省1.8至360万里拉。建议分销公司使用数字仪表代替机电仪表,特别是对于大中型消费者。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号