首页> 外文会议>Indoor Air 2005 >DUTCH DAYCARE CENTERS: HOT AND STUFFY
【24h】

DUTCH DAYCARE CENTERS: HOT AND STUFFY

机译:荷兰的日托中心:热和坚固

获取原文

摘要

Young children spend a lot of time in daycare centers. It is known that a bad indoor environment can cause health problems. This paper describes an investigation of the indoor environment in Dutch daycare centers. The study includes summer and winter measurements of the air temperature and the absolute CO2 levels in 14 daycare centers. The results showed that during winter in 34% of all spaces the maximum CO2 limit of 1000 ppm was exceeded. In summer the CO2 levels stay beneath 1000 ppm in most spaces but it is too hot (in 70% of all bedrooms measured air temperature exceeded recommended value). The main causes are that daycare centers are mostly housed in naturally ventilated buildings which depend on adequate ventilation devices and on adequate sun shading, which are both lacking in most cases. Most important recommendations: adequate ventilation devices by adding facade-vents and mechanical exhaust systems, install sun-screen and instruction to the staff.
机译:幼儿在日托中心花费很多时间。众所周知,恶劣的室内环境会导致健康问题。本文介绍了对荷兰日托中心室内环境的调查。该研究包括夏季和冬季在14个日托中心的气温和绝对CO2水平的测量。结果表明,在冬季,所有空间的34%都超过了1000 ppm的最大CO2限值。在夏季,大多数空间中的CO2含量都保持在1000 ppm以下,但温度太高(在70%的卧室中,测得的气温超过了建议值)。主要原因是日托中心大多位于自然通风的建筑物中,这些建筑物依赖于充足的通风设备和充足的遮阳设施,而在大多数情况下都缺乏。最重要的建议:增加外墙通风和机械排气系统,以提供足够的通风设备,并安装防晒霜并向工作人员提供指导。