Our test apparatus was able to test multi-split system air-conditioners and the packaged type air-conditioners with varying thermal load conditions. Using our test apparatus, tests of the multi-split system and the packaged type electric air-conditioners (both types of thermal storage and non-storage), gas engine air-conditioners were performed. It was made clear that the electric air-conditioners were superior to the gas engine air-conditioners in the performance characteristics. As a result, the cooling and heating capacity ratio of the measured values to the specific values was over 95% for the electric air-conditioners and about 80% for the gas engine air-conditioners. The primary energy efficiency was 0.7-1.2 for the electric air-conditioners and 0.6-0.8 for the gas engine air-conditioners.
机译:我们的测试设备能够测试具有不同热负荷条件的多分体式空调器和组合式空调器。使用我们的测试设备,对多分裂系统和组合式电动空调(蓄热和非存储两种类型),燃气发动机空调进行了测试。很明显,电动空调的性能优于燃气发动机。结果,对于电动空调而言,测量值与特定值的制冷和制热能力比超过95%,而对于燃气发动机空调而言,约为80%。电动空调的一次能效为0.7-1.2,燃气发动机空调的一次能效为0.6-0.8。