DESIGN, FABRICATION AND TESTING OF AN INFRARED RATIO PYROMETER SYSTEM FOR THE MEASUREMENT OF GASIFIER REACTION CHAMBER TEMPERATURE – A STATUS REPORT

机译:测量气化炉反应室温度的红外比率热释光系统的设计,制造和测试–状态报告

获取原文

摘要

A reliable measurement of the temperature inside the reaction chamber of an entrained-flow gasifier isvery important. This is because the temperature must be maintained within a narrow range. The upperbound is set by the need to limit the rate of refractory deterioration. The lower bound is set by the needto control the viscosity of the slag to a low enough value so that it will flow down the wall and, thus,ensure adequate slag removal through the bottom of the reactor. In addition, an accurate knowledge ofgasifier temperature is very important during gasifier startup. And, during normal operation, thetemperature instrumentation must provide a rapid and reliable indication of deviation from normaloperation, such as a failure of one of the feed systems or a sudden change in feed quality.ChevronTexaco's Montebello Technology Center (MTC) has developed an infrared ratio pyrometersystem for measuring gasifier reaction chamber temperature. The system attaches to the gasifier usingone of the sidewall nozzles normally used for gasifier thermocouples. It views the interior of therefractory lined gasifier reaction chamber through a purged, optical access port. This system has afaster response time than both thermocouples and inferential techniques using syngas methanemeasurements, and has been demonstrated to provide reliable temperature measurements for longerperiods of time when compared to thermocouples installed in the same gasifier. In addition, the systemcan be applied to commercial gasifiers without any significant scale-up problems.Under the auspices of DOE Cooperative Agreement No. DE-FC26-99FT-40684, ChevronTexacohas constructed a commercial prototype of this pyrometer system for field testing in a commercialgasification plant. The major equipment items, the purge system and the safety shutdown system areessentially identical to the installations in the pilot units, with a few key modifications.This paper explains the problem of temperature measurement in entrained-flow gasifiers and describesthe pyrometer system developed by ChevronTexaco. It also goes on to describe the commercialprototype which has been built, and the commercial gasification plant field test, which is currently beingplanned.
机译:气流床气化炉反应室内温度的可靠测量是 很重要。这是因为温度必须保持在窄范围内。上层 限制是由需要限制耐火材料的劣化速率来确定的。下限由需要设置 将炉渣的粘度控制到足够低的值,以便炉渣顺着壁流下,因此, 确保通过反应器底部充分除去炉渣。此外,对 气化炉启动期间气化炉温度非常重要。并且,在正常运行期间, 温度仪表必须提供快速可靠的偏离正常值的指示 操作,例如进纸系统之一发生故障或进纸质量突然变化。 雪佛龙德士古的蒙特贝罗技术中心(MTC)开发了一种红外比率高温计 用于测量气化炉反应室温度的系统。该系统通过以下方式连接到气化炉 通常用于气化炉热电偶的侧壁喷嘴之一。它可以看到内部 耐火衬里气化炉反应室通过吹扫的光学通道进入。这个系统有一个 比使用合成气甲烷的热电偶和推论技术都更快的响应时间 测量,并已被证明可以提供更长时间的可靠温度测量 与安装在同一气化炉中的热电偶相比的时间间隔。另外,系统 可以应用于商业气化炉,而没有任何明显的扩大问题。 在美国能源部合作协议号DE-FC26-99FT-40684的主持下,雪佛龙德士古 已经建造了该高温计系统的商业原型,用于在商业环境中进行现场测试 气化厂。主要设备项目包括吹扫系统和安全关闭系统 与先导装置的安装基本相同,但有一些关键的修改。 本文解释了气流床气化炉中温度测量的问题并描述了 雪佛龙德士古开发的高温计系统。它也继续描述了商业广告 已建造的原型,以及目前正在进行的商业气化厂现场测试 计划。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号