In refrigeration systems a small amount of compressor lubricant is entrained in the refrigerant and circulated through the system, where some is retained in each component. The suction line to the compressor has the largest potential for oil retention. This paper presents results from an experimental apparatus that has been constructed to circulate POE (polyolester) oil and R410A at a controlled mass flux, OCR (oil in circulation ratio), and superheat, and to directly measure the pressure drop and mass of oil retained in horizontal and vertical suction lines. The bulk vapor velocity and overall void fraction are determined from direct mass and temperature measurements. The oil retention, pressure drop, and flow regimes near the minimum ASHRAE recommended vapor velocity condition are explored, in order to better understand and define these conditions.
机译:在制冷系统中,少量的压缩机润滑剂被吸入制冷剂中并在系统中循环,其中的一些润滑剂保留在每个组件中。通往压缩机的吸油管具有最大的保油潜力。本文介绍了一种实验设备的结果,该设备经构造可在受控的质量通量,OCR(循环油比)和过热度下循环POE(多酯)油和R410A,并直接测量压降和保留的油的质量在水平和垂直吸力管中。总体蒸气速度和总空隙率由直接的质量和温度测量值确定。为了更好地理解和定义这些条件,研究了在最低ASHRAE建议的蒸汽速度条件附近的油保持力,压降和流态。