首页> 外文会议>Electrical/Electronics Insulation Conference >Effect of solid impurities on power frequency breakdown strength in compressed air in uniform, non-uniform and co-axial fields
【24h】

Effect of solid impurities on power frequency breakdown strength in compressed air in uniform, non-uniform and co-axial fields

机译:均匀,不均匀和同轴电场中固体杂质对压缩空气中工频击穿强度的影响

获取原文

摘要

Solid impurities such as micronised metallic particles in a Compressed Gas Insulated System (GIS) are detrimental to system performance. Detailed studies were conducted to quantify the extent of reduction in 50 Hz power frequency breakdown strength due to the presence of free and fixed conducting particles (0.4 mm dia × 4 mm length) and variation of particle length (4 mm, 5 mm and 6 mm) in compressed air in uniform, non-uniform and co-axial fields. The stud1es were conducted for pressures varying from 100 to 500 kPa and electrode gap varying from 10 to 50 mm. The experimental results indicate that the reduction in breakdown strength (BDS) due to the presence of fixed conducting particle is predominant (> 50%) in uniform and co-axial fields, whereas, it is very nominal (<10%) in non-uniform field. The reduction is found to increase with the increase in length of the fixed conducting particle. The reduction, in general, decreases with increase in gap length and pressure, but the variation is random in non-uniform field. In case of free conducting particle the reduction is more than the fixed one in the electrode system.
机译:压缩气体绝缘系统(GIS)中的固体杂质(如微粉化的金属颗粒)会损害系统性能。进行了详细的研究,以量化由于存在自由和固定的导电颗粒(直径0.4 mm×长度4 mm)和颗粒长度变化(4 mm,5 mm和6 mm)而导致的50 Hz工频击穿强度降低的程度。 )在压缩空气中均匀,不均匀和同轴的场中。在压力为100至500 kPa和电极间隙为10至50 mm的条件下进行螺柱。实验结果表明,由于固定导电粒子的存在,击穿强度(BDS)的降低在均匀和同轴磁场中占主导地位(> 50%),而在非均匀和同轴磁场中则非常明显(<10%)。统一领域。发现减少量随着固定导电颗粒的长度的增加而增加。通常,减少量随着间隙长度和压力的增加而减少,但在非均匀场中变化是随机的。在自由导电粒子的情况下,减少量要大于电极系统中固定的减少量。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号