首页> 外文会议>IEEE International Symposium on Electrical Insulation >Applications of Insulation Resistance and High Direct Voltage Ramp Tests to the Assessment of Insulation Systems of Hydrogenerator Stator Bars and Coils
【24h】

Applications of Insulation Resistance and High Direct Voltage Ramp Tests to the Assessment of Insulation Systems of Hydrogenerator Stator Bars and Coils

机译:绝缘电阻和高直接电压斜坡试验对氢化机定子杆和线圈绝缘系统的应用

获取原文

摘要

The paper discusses the application of the insulation resistance and polarization index and the high direct voltage ramp tests to the assessment of the integrity of insulation of hydrogenerator stator bars and coils. In the paper, examples of continuously recorded insulation resistance and current measured during the high direct voltage ramp tests are presented for epoxy-mica insulated stator bars of hydrogenerators. The paper defines also new parameters for the interpretation and comparison of various test data obtained from the insulation resistance and the high direct voltage ramp tests.
机译:本文讨论了绝缘电阻和偏振指数的应用以及高直接电压斜坡试验对氢化机构杆和线圈绝缘的完整性的评估。本文在高直接电压斜坡试验期间测量的连续记录的绝缘电阻和电流的实例用于氢化器的环氧树脂 - 云母绝缘定子条。本文还定义了用于解释的新参数,以及从绝缘电阻和高直接电压斜坡测试中获得的各种测试数据的比较。

著录项