The authors present data obtained from tests conducted on an SF/sub 6/ GIS (gas-insulated switchgear) model, 123 kV, having coaxial cylinders of 240/80-mm diameter in the presence of mobile particles. In the case of a vertical GIS construction and in the presence of conducting particles, a great hazard to the insulation is shown to occur when overvoltages appear in service. There is a wide range of imminent particles since heavy and light particles are included. The presence of conducting particles in the case of a conic spacer insulator also causes a hazard to insulation due to overvoltages appearing in service. The detection of particles left after final assembly on site and of those located on the spacer insulators which were tested in 123-kV GIS is possible using tests with applied 185 kV AC voltage and tests with impulse voltage at 80% basic insulation level.
机译:作者提出了从在SF / Sub 6 / GIS(气体绝缘开关设备)模型,123kV上进行的测试中获得的数据,其在移动颗粒存在下具有240 / 80mm直径的同轴圆柱体。在垂直的GIS构建和在导电颗粒存在的情况下,当过电压出现在服务中时,将显示对绝缘体的巨大危害。由于包括重和光颗粒,因此存在各种迫在眉睫的颗粒。在圆锥间隔物绝缘体的情况下,在圆锥形隔离器的情况下存在导致由于服务中出现的过电压而导致绝缘的危害。使用施加的185kV AC电压的试验和80%基本绝缘水平的脉冲电压测试,在位于部位和位于123 kV GIS中测试的间隔内绝缘体上的那些在123 kV GIS上进行测试的那些在123 kV GIS上进行测试的颗粒检测。