首页> 外文会议> >Determination of phase sequence and voltage level of high-voltage double-circuit overhead conductors using non-contact technique
【24h】

Determination of phase sequence and voltage level of high-voltage double-circuit overhead conductors using non-contact technique

机译:非接触技术确定高压双回路架空导线的相序和电压电平

获取原文

摘要

Determination of phase sequence and voltage level of double-circuit overhead conductors is investigated using non-contact sensors situated on a moving platform at ground level. Based on the investigation of the electric field beneath double-circuit transmission lines through finite element analysis (FEA) simulations and laboratory experiments with a scale model, a determination methodology is proposed. Experiments taken beneath 400 kV double-circuit transmission lines are presented in detail. Analysis of the experimental results shows that the proposed determination methodology can successfully evaluate the phase sequence arrangement and voltage level of high-voltage double circuit conductors.
机译:使用位于地面的移动平台上的非接触式传感器,研究了确定双回路架空导线的相序和电压水平的方法。在通过有限元分析(FEA)模拟和规模模型实验室实验对双回线传输线下方的电场进行调查的基础上,提出了一种确定方法。详细介绍了在400 kV双回输电线路下进行的实验。对实验结果的分析表明,所提出的确定方法能够成功地评估高压双回路导体的相序排列和电压水平。