Diagnosis of Power Transformer Faults Based On Fuzzy Three-Ratio Method

机译:基于模糊三比率法的电力变压器故障诊断

获取原文

摘要

Dissolved gas-in-oil analysis (DGA) is one of the most useful methods to detect transformer incipient faults. Among the diverse conventional DGA methods, IEC three-ratio method is widely used, but in many cases this method can not accurately diagnose(such as no matching, multiple faults). This paper proposes a fuzzy three-ratio method; it is considered that the drawbacks of the conventional three-ratio method lie in: when the ratio crosses the coding boundary, codes change sharply, but in reality the boundary should be fuzzied. Based on this assumption, this paper first propose the fuzzy membership functions for codes "zero","one","two", then it transfer the conventional logic "AND" and "OR" used in IEC three-ratio method into fuzzy logic and put forward the diagnosing steps of this method. Simulation proves the proposed method can overcome the drawbacks of the conventional three-ratio method that can not diagnose multi-fault and no matching codes for diagnosis, thus, it greatly enhanced diagnosing accuracy.
机译:溶解的气体分析(DGA)是检测变压器初期断层的最有用方法之一。在多种传统的DGA方法中,IEC三相方法被广泛使用,但在许多情况下,这种方法无法准确诊断(例如无匹配,多个故障)。本文提出了一种模糊三相法;据认为,传统三比例方法的缺点位于:当该比率交叉编码边界时,代码急剧地变化,但实际上应该模糊边界。基于此假设,本文首先提出了代码“零”,“一个”,“二”,然后它将传统逻辑“和”或“在IEC三比例中使用的模糊隶属函数提出了模糊逻辑并提出了这种方法的诊断步骤。仿真证明了所提出的方法可以克服传统三维方法的缺点,该方法不能诊断多故障,因此没有匹配码的诊断,从而大大提高了诊断精度。