The paper introduces the basic structure and equivalent circuit model of unified power flow controller (UPFC) and then analyzes its effects on the transmission line distance relay in two cases. Different location of the UPFC, fault resistance, parameters of UPFC, the location of the fault and system operation conditions all affect the measured apparent impedance to some degree. The presence of UPFC will make the relay under-reach or over-reach. In order to eliminate the effects of a UPFC device on protective relay, two methods are given in this paper. One is to equip protective relay devices in which the UPFC device is equipped. In this way the UPFC device is always beyond the fault loop. The other is to use an artificial neural network to eliminate the effects of UPFC device.
机译:介绍了统一潮流控制器UPFC的基本结构和等效电路模型,然后分析了这两种情况对输电线路距离继电器的影响。 UPFC的不同位置,故障电阻,UPFC的参数,故障的位置以及系统的运行状况都会在一定程度上影响所测的视在阻抗。 UPFC的存在将使中继无法到达或超过。为了消除UPFC装置对保护继电器的影响,本文给出了两种方法。一种是装备装有UPFC装置的继电保护装置。这样,UPFC设备始终位于故障回路之外。另一种是使用人工神经网络来消除UPFC设备的影响。

著录项