摘要

Distribution functions of both current loads and absorbed energies are obtained in arresters installed on towers of overhead lines (OHLs) with 500 and 1150 kV line voltages. To determine these characteristics, a procedure was used which took account of the orientation of lightning leader channel in the thundercloud/OHL system. The employment of the technique in question is shown to be capable of offering both not very stringent requirements to protection devices and improved scheme of line rope suspension on OHL which ensures the lowest probability of lightning breaking through the rope protection system.
机译:电流负载和吸收的能量的分布函数都是通过安装在具有500和1150 kV线路电压的架空线路(OHL)塔上的避雷器获得的。为了确定这些特征,使用了考虑雷云/ OHL系统中的雷电引导通道方向的过程。该技术的使用显示出既可以对保护装置提出不很严格的要求,又可以对OHL上的绳索悬吊进行改进,从而确保了雷电突破绳索保护系统的可能性最低。