首页> 外文会议> >System protection and control task force's initial recommendations concerning NERC recommendation 8A loadability requirements on transmission protective relaying systems
【24h】

System protection and control task force's initial recommendations concerning NERC recommendation 8A loadability requirements on transmission protective relaying systems

机译:系统保护和控制工作队关于NERC建议8A对变速器保护继电系统的负载能力要求的初始建议

获取原文

摘要

This paper discusses with system protection and control task force's initial recommendations concerning with NERC recommendation 8A loadability requirements on transmission protective relaying systems. The NERC investigation team recommends that the zone 3 relay, if used, should not operate at or below 150% of the emergency ampere rating of a line, assuming a .85 per unit voltage and a line phase angle of 30 degrees. The planning committee shall review such exceptions to ensure they do not increase the risk of widening a cascading failure of the power system.
机译:本文与系统保护和控制工作队的初步建议一起讨论,这些建议与NERC建议8A对变速器保护继电系统的负载能力要求有关。 NERC调查小组建议,如果使用3区继电器,则在每单位电压为0.85且线路相角为30度的情况下,不应在线路的紧急安培额定值的150%或以下运行。规划委员会应审查此类例外情况,以确保它们不会增加扩大电源系统级联故障的风险。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号