The paper presents experimental measuring results of the ion decay time during the post-arc phase after a forced interruption of diffuse vacuum arc. Arc current of amplitudes 400 A and 600 A was switched-off using counter-pulse current with falling rates from 2 A//spl mu/s u to 67 A//spl mu/s in a laboratory test circuit. The used voltage, current and contact parameters were representative for a low-voltage vacuum switch. The decay process of ion current was observed, using a retarding field analyser. First, a series of introductory measurements concerning probe calibration were performed. The decay times of ions were measured as function of the falling rate of the counter-current, and mean values from about 60 /spl mu/s at arc current falling rate 2 A//spl mu/s up to 35 /spl mu/s at arc current falling rate 67 A//spl mu/s were measured. Only a small dependence of the decay time from the arc current value (400 A or 600 A) was observed. The decay time decreases significantly with increasing of the counter-current failing rate. The results are proposed as a parameter in the modelling of post-arc phenomena of low voltage vacuum switches.
机译:本文介绍了在强制中断弥散真空电弧后电弧后阶段离子衰减时间的实验测量结果。在实验室测试电路中,使用反脉冲电流以2 A // splμs/ s u到67 A // splμs/ s的下降速率关闭了振幅为400 A和600 A的电弧电流。所用的电压,电流和接触参数代表低压真空开关。使用延迟场分析仪观察到离子电流的衰减过程。首先,进行了一系列与探头校准有关的介绍性测量。测量离子的衰变时间作为逆流下降速率的函数,其平均值从电弧电流下降速率2 A // spl mu / s时的约60 / spl mu / s到35 / spl mu / s在电弧电流下降速率下的s为67A //splμs/ s。观察到的衰减时间与电弧电流值(400 A或600 A)的关系很小。随着逆流故障率的增加,衰减时间显着减少。建议将结果作为低压真空开关弧后现象建模的参数。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号