This paper presents the enhancement of power system stability for a large industrial customer when a new cogeneration unit with 40 MW capacity has been added to the system. The proper settings of protective relays have been designed according to the transient stability analysis. For the severe nearby fault, the under frequency relay are applied for the isolation of the industrial power system and for the load shedding so that the tripping of the regeneration units can be prevented and the critical loads can be maintained. To verify the effectiveness of the proposed protective scheme, the computer simulation of the industrial power system under various load levels and fault cases has been performed. It is concluded that the system stability of the industrial customer can be improved by the proper design of protective schemes.
机译:本文提高了大型工业客户的电力系统稳定性,当时已添加40兆瓦的新兴电机单元。根据瞬态稳定性分析设计了保护继电器的适当设置。对于严重的附近故障,施加下频率继电器用于隔离工业电力系统和负载脱落,从而可以防止再生单元的跳闸,并且可以保持临界载荷。为了验证所提出的保护方案的有效性,已经进行了各种负载水平和故障情况下的工业电力系统的计算机模拟。得出结论,工业客户的系统稳定性可以通过适当的保护方案设计来改善。