首页> 外文会议> >Causes and control of common-mode transients induced by fuse-blowing in battery plants
【24h】

Causes and control of common-mode transients induced by fuse-blowing in battery plants

机译:电池工厂中熔丝熔断引起的共模瞬变的原因和控制

获取原文
获取外文期刊封面目录资料

摘要

Common-mode transients can be induced when protection devices such as fuses or circuit breakers blow due to faults that occur between the feeder and ground. Such transient voltages can be substantially larger than the powering voltage and could lead to breakdown of equipment. The mechanisms that cause these transients and a method for limiting the transients to safe levels are described using experimental measurements from an actual plant and simulation models. The impact of different fuse characteristics on the transients is also discussed.
机译:当保护装置(例如保险丝或断路器)由于馈线与地面之间发生的故障而烧断时,可能会引起共模瞬变。这样的瞬态电压可能会比供电电压大得多,并可能导致设备故障。使用来自实际工厂的实验测量和仿真模型,描述了导致这些瞬变的机制以及将瞬变限制在安全水平的方法。还讨论了不同熔断器特性对瞬态的影响。