Thermal problems caused by harmonic frequency leakage fluxes in 3-phase, 3-winding converter transformers

机译:三相三绕组换流变压器中谐波泄漏磁通引起的热问题

获取原文

摘要

Harmonic frequency leakage flux can be a limiting factor in 3-phase, 3-winding HVDC converter transformers. Investigation of a 3-phase, 3-winding 240 MVA converter transformer failure indicated the failure was caused by harmonic fluxes. Calculations indicated that the magnitudes of these harmonic fluxes to be approximately 45% of the power frequency leakage flux for the transformer, and are little affected by the transformer impedance or the converter firing angle. A study of the failed transformer loading during its life was made, and a calculation made of the hot spot temperature considering various insulation half-life factors. Based on published information on insulation half-life factors it was estimated that at full load the hot spot temperature of the transformer was about 159/spl deg/C. From examination of the insulation in the hot spot area, this estimate of hot spot temperature was considered reasonable.
机译:在三相三绕组HVDC转换器变压器中,谐波频率漏磁通可能是一个限制因素。对三相3绕组240 MVA转换器变压器故障的调查表明,该故障是由谐波磁通引起的。计算表明,这些谐波磁通量的大小约为变压器工频泄漏磁通量的45%,并且几乎不受变压器阻抗或转换器点火角的影响。对变压器在其寿命期间的失效负载进行了研究,并对考虑了各种绝缘半衰期因素的热点温度进行了计算。根据有关绝缘半衰期因素的公开信息,估计在满载条件下,变压器的热点温度约为159 / spl deg / C。通过检查热点区域的绝缘材料,可以认为热点温度的这种估计是合理的。