Fault component negative-sequence direction (FCNSD) relays only need three phases voltages and currents at generator terminals, and can detect various asymmetrical faults in generators with a very high sensitivity. In this paper, the instantaneous negative-sequence symmetrical components, which are based on the Lyon transform an used in the FCNSD relay. From the results of tests on a laboratory generator-transformer unit, it is found that there are very large harmonic constituents in the Lyon component power values. The mechanism of these harmonic constituents is theoretically derived in the paper. To eliminate the influence of the harmonic constituents, a new criteria is proposed-fault component negative-sequence energy direction (FCNSED) protection.
机译:故障分量负序方向(FCNSD)继电器在发电机端子上仅需要三相电压和电流,并且能够以很高的灵敏度检测发电机中的各种非对称故障。在本文中,瞬时负序对称分量是基于FCNSD继电器中使用的Lyon变换的。根据实验室发电机-变压器单元的测试结果,发现里昂分量功率值中有非常大的谐波成分。从理论上推导了这些谐波成分的机理。为了消除谐波成分的影响,提出了一种新的标准-故障分量负序能量方向(FCNSED)保护。