Since 1978, the Hong Kong Electric Company Limited (HEC) has switched to the use of 11 kV vacuum circuit breakers (VCB) in both new projects of primary substations and uprating of existing primary substations. From then on the population of oil circuit breakers (OCB) diminished. By 1989, there were approximately 600 VCBs in the 11 kV system. The in-service OCBs were reduced to some 410 pieces and were supplied by two manufacturers in late 1960s and early 1970s. Both manufacturers were asked to inspect the busbars and housing of the switchboards, and confirm that the residual life was more than fifteen years. The simple and economical way of upgrading is to replace the oil circuit breaker carriages without disturbing the busbars. The author describes the joint efforts devoted by switchgear manufacturers and HEC to design and type test replacement vacuum breakers to achieve cost-effectiveness and minimal supply interruption. Experience of the breaker replacement and the saving in operational costs after employment of vacuum breakers are also presented.
机译:自1978年以来,香港电气有限公司(HEC)在主要变电站的新项目和现有主要变电站的升级改造中都已改用11 kV真空断路器(VCB)。从那时起,石油断路器(OCB)的数量开始减少。到1989年,在11 kV系统中大约有600个VCB。在役的OCB减少到了410片,由两家制造商在1960年代末和1970年代初提供。两家制造商都被要求检查配电盘的母线和外壳,并确认剩余寿命超过十五年。简单而经济的升级方法是在不干扰母线的情况下更换机油断路器支架。作者介绍了开关设备制造商和HEC共同努力设计和测试替代真空断路器的类型,以实现成本效益和最小的电源中断。还介绍了使用真空断路器后更换断路器的经验以及节省操作成本的经验。