首页> 外文会议>Limited Motion Electrical Actuation Systems >Development of adaptive protection scheme for distribution systems with high penetration of distributed generation
【24h】

Development of adaptive protection scheme for distribution systems with high penetration of distributed generation

机译:分布式发电高渗透率配电系统自适应保护方案的开发

获取原文
获取原文并翻译 | 示例

摘要

Conventional power distribution system is radial in nature, characterized by a single source feeding a network of down-stream feeders. Protection scheme for distribution system, primarily consisting of fuses and reclosers and in some cases, relays, has traditionally been designed assuming the system to be radial. After connecting distributed generation (DG), part of the system may no longer be radial, which means the coordination might not hold. The effect of DG on coordination will depend on size, type and placement of DG. This paper explores the effect of high DG penetration on protective device coordination and suggests an adaptive protection scheme as a solution to the problems identified. Results of implementation of this scheme on a simulated actual distribution feeder are reported.
机译:传统的配电系统本质上是放射状的,其特征在于向下游馈线网络馈电的单个电源。配电系统的保护方案主要由保险丝和重合闸组成,有时还包括继电器,传统上是在系统呈放射状的情况下设计的。连接分布式发电(DG)后,系统的一部分可能不再是径向的,这意味着可能无法保持协调。 DG对协调的影响将取决于DG的大小,类型和位置。本文探讨了高DG渗透对保护设备协调的影响,并提出了一种自适应保护方案来解决所发现的问题。报告了该方案在模拟的实际配电馈线上实施的结果。