Analysis of the 6kV System Overvoltage Caused by the Input of the 35kV Vacuum Circuit Breaker

机译:35kV真空断路器输入引起的6kV系统过电压分析

获取原文
获取原文并翻译 | 示例

摘要

In this paper we analyze possible causes of the Very Fast Transient Overvoltage (VFTO for short), which can be found occasionally when an SVC is brought into service by a vacuum breaker. Using EMTP, a simulation model is built based on a practical and simplified application. Two possible causes are found accordingly. One is the resonance of the circuit oscillation and the VFTO in power cables, and correspondingly a rule of fault identification is given. The other is the undersize direct-to-ground capacity of the transformer's 6kVside, and a method is introduced to evaluate the effect when using another capacitor bank to limit the peak value of VFTO.
机译:在本文中,我们分析了超快速瞬态过电压(简称VFTO)的可能原因,当真空断路器将SVC投入使用时,偶尔会发现这种情况。使用EMTP,可以基于实际和简化的应用程序构建仿真模型。因此找到两个可能的原因。一种是电力电缆中电路振荡和VFTO的谐振,并相应地给出了故障识别的规则。另一个是变压器6kV侧的过小的直接接地容量,并且引入了一种方法来评估使用另一个电容器组限制VFTO峰值时的影响。