Lightning Current Distribution inside of Directly Hit Building

机译:直击建筑物内部的雷电流分布

获取原文

摘要

Lightning current distribution inside of a directly hit building is calculated by an electromagnetic model with the help of Numerical Electromagnetic Code (NEC-4). Portions of lightning current into wirings protected by SPD are evaluated. Representative values of the portions are determined in the frequency domain. The portions into wirings on the top floors or on the first floors are largest irrespective of height of the building. Those into wirings on the middle floors are negligibly small. This result is useful in determining energy ratings of SPD.
机译:借助数字电磁代码(NEC-4),通过电磁模型计算直接击中建筑物内部的雷电流分布。评估雷电电流进入受SPD保护的布线部分。在频域中确定部分的代表值。无论建筑物的高度如何,顶层或二层的布线部分最大。在中层布线的电缆很小,几乎可以忽略不计。此结果对于确定SPD的能量额定值很有用。