CONTROLS OF MULTIPLE CHILLERS IN CENTRAL COOLING PLANTS

机译:中央冷却设备中多个冷却器的控制

获取原文
获取原文并翻译 | 示例

摘要

This paper summarizes the results of an extensive parametric analysis to assess the potential of multi-chiller plants to save energy associated with electric cooling use. Specifically, the impacts on chiller performance are investigated for two office buildings geometries, three chiller types, and five geographical locations. It was determined that for most office buildings, increasing the number of chillers beyond three does not provide significant additional energy savings for all three types of chillers and for all locations. Moreover, the results of the analysis indicate that a chiller size ratio of 0.65 for the case of a two-chiller central cooling plants provides the optimal energy performance.
机译:本文总结了广泛的参数分析结果,以评估多冷水机组节省与电冷却相关的能源的潜力。具体来说,研究了两种办公楼的几何形状,三种冷水机类型和五个地理位置对冷水机性能的影响。已确定,对于大多数办公楼而言,将冷水机数量增加到三个以上并不能为所有三种冷水机以及所有位置提供大量的额外节能。此外,分析结果表明,对于两台冷却器的中央冷却装置,冷却器的尺寸比为0.65,可提供最佳的能源性能。