【24h】

MICROCHANNEL EVAPORATORS OF THE RESIDENTIAL AIR-CONDITIONER

机译:住宅空调的微通道蒸发器

获取原文
获取原文并翻译 | 示例

摘要

The objective of present work was to evaluate the performance of microchannel evaporators of the residential air-conditioner using R-22. Six prototype evaporators were manufactured and tested with psychrometric calorimeter test facilities. The test was conducted in two different ways. Each evaporator consisted of two parallel flow type heat exchangers connected with several return pipes. The heat exchanger had 41 microchannel tubes that had 8 rectangular ports with the hydraulic diameter of 1.3 mm. For the vapor compression system(VCS), the flow area ratio and the number of return pipe had a great effect on the cooling capacity. Type 3 with the flow area ratio of 73/ 58% showed best cooling capacity. The effect of the number of circuit and merging manifold on the cooling capacity was relatively small. For the refrigerant circulation system(RCS), the cooling capacity of the test evaporators was a little bit changed as the mass flow rate and inlet quality increased. The effect of mass flow rate on the cooling capacity was slightly superior to that of inlet quality. The effect of the number of circuit on the cooling capacity was different with the result of the VCS, while the effect of merging manifold was negligible. The cooling capacity proportionally increased as the vertical inclination angle of the evaporator increased due to gravity force.
机译:当前工作的目的是评估使用R-22的家用空调微通道蒸发器的性能。制造了六台原型蒸发器,并使用干热法测试设备进行了测试。该测试以两种不同的方式进行。每个蒸发器由两个平行流式热交换器组成,热交换器与多个回流管相连。热交换器具有41个微通道管,这些微通道管具有8个矩形端口,水力直径为1.3毫米。对于蒸气压缩系统(VCS),流量比和回流管数量对冷却能力有很大影响。流动面积比为73/58%的类型3显示出最佳的冷却能力。回路数量和合并歧管数量对冷却能力的影响相对较小。对于制冷剂循环系统(RCS),随着质量流量和入口质量的增加,测试蒸发器的冷却能力略有变化。质量流量对冷却能力的影响略优于进口质量。回路数量对冷却能力的影响与VCS的结果不同,而合并歧管的影响则可忽略不计。由于重力的作用,冷却能力随着蒸发器的垂直倾斜角度的增加而成比例地增加。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号