A large share of energy consumption is taken by an air-conditioning system. It worsens the electricity load of the power network. Therefore, more and more scholars are paying attention to research on new types of air-conditioning systems that are energy-saving and environment-friendly. A liquid desiccant air conditioning system is among them, as it has a tremendous ability for power storage and low requirements for heat resources. Heat with low temperatures, such as excess heat, waste heat, and solar power, is suitable for the liquid desiccant air-conditioning system. The feasibility and economical efficiency of the system are studied in this experimental research. The result shows that when the temperature of the regeneration is about 80℃, the thermodynamic coefficient of the system is about 0.6, and the supply air temperature of the air-conditioning system remains stable at 21℃, the air-conditioning system can meet human comfort levels.
机译:空调系统消耗了很大一部分能源。这会使电网的电力负荷恶化。因此,越来越多的学者开始关注节能环保的新型空调系统的研究。其中包括液体干燥剂空调系统,因为它具有强大的蓄电能力和对热资源的低要求。低温热量(例如多余的热量,废热和太阳能)适合用于液体干燥剂空调系统。本实验研究了该系统的可行性和经济性。结果表明,当再生温度为80℃左右时,系统的热力学系数为0.6左右,空调系统的送风温度稳定在21℃左右,可以满足人体的需求。舒适度。