Energy Consumption Measuring and Diagnostic Analysis of Air-conditioning Water System in a Hotel Building in Harbin

机译:哈尔滨某宾馆建筑空调水系统能耗测量与诊断分析

获取原文
获取原文并翻译 | 示例

摘要

This paper introduces an air-conditioning water system in a hotel building in Harbin, finishes its air-conditioning energy consumption measurement in summer conditions, and presents an estimation index of performance of chiller, pump and motor. By means of testing data analysis, it is indicated that several problems such as unsuitable operation schedule of the chiller, low COP, irrational matching of pump and motor, unbalanced conditions of chilled water flow, and low working stability and efficiency ratio of the pump are existent. The paper presents suggestions for improvement with relevance based on the induction and analysis of system fault found in measurements.
机译:本文介绍了哈尔滨某饭店楼的空调水系统,在夏季条件下完成了空调能耗的测量,并给出了冷水机,水泵和电动机的性能评估指标。通过测试数据分析表明,存在以下问题:冷水机组运行时间表不合适,COP低,泵与电动机的不匹配,冷水流量不平衡,泵的工作稳定性和效率比低。存在。本文基于对测量中发现的系统故障的归纳和分析,提出了相关的改进建议。