首页> 外文会议>International Institute of Refrigeration;IIR International congress of refrigeration;Ministry of Economy, Trade and Industry;Ministry of Agriculture, Forestry and Fisheries >EXPERIMENTAL INVESTIGATIONS ON PERFORMANCE OF EVAPORATOR AND CONDENSER OF R410A INSIDE A NOVEL BRAZED PLATE HEAT EXCHANGER
【24h】

EXPERIMENTAL INVESTIGATIONS ON PERFORMANCE OF EVAPORATOR AND CONDENSER OF R410A INSIDE A NOVEL BRAZED PLATE HEAT EXCHANGER

机译:新型钎焊板式换热器内R410A蒸发器和冷凝器性能的实验研究

获取原文

摘要

A novel technology on plate heat exchanger was introduced. Heat transfer and pressure loss wereinvestigated with water flow through dimple plate and herringbone plate as well as R410A flow boiling andcondensing. Experiments on three kinds of plate patterns (one herringbone plate, one normal dimple plateand one novel dimple plate) were performed based on given heat flux (6~14 kW/m~2), comparatively. Testresults with single phase flow and condenser showed that two given dimple plates have high heat transferefficiency with low pressure loss under same conditions and capacity due to unique channel and cell design.For evaporator application, the normal dimple plate becomes worse due to poor refrigerant distribution overplate surface compared with herringbone plate. However, the unique dimple plate achieved extremely goodperformance with low pressure loss due to good distribution and high efficiency of heat transfer cell. Inaddition, the dimple plate can provide more flexible and specified design according to application conditionfrom customers.
机译:介绍了一种板式换热器的新技术。通过水流通过凹板和人字形板以及R410A流动沸腾和冷凝,研究了传热和压力损失。分别根据给定的热通量(6〜14 kW / m〜2)对三种板型进行了实验(一种人字形板,一种普通酒窝板和一种新型酒窝板)。单相流和冷凝器的测试结果表明,由于独特的通道和单元设计,两个给定的凹窝板在相同条件和容量下在相同条件和容量下具有较高的传热效率和较低的压力损失。表面与人字形板相比。然而,由于传热单元的良好分布和高效率,独特的凹坑板在极低的压力损失下实现了极好的性能。另外,根据客户的使用条件,凹坑板可以提供更灵活和特定的设计。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号