【24h】

A COMPARATIVE STUDY ON THE OPTIMUM PERFORMANCE OF R410A AND R32 REFRIGERATION CYCLES

机译:R410A和R32制冷循环的最佳性能比较研究

获取原文

摘要

The optimum performance of R410A and R32 refrigeration cycles is studied in this paper. A theoretical model for the coefficient of performance is derived first. Then, the L_9(3~4) orthogonal table of Taguchi method is used for performance analysis. In the experimental design, four factors and three levels are considered. The range of each factor is given as: 0.8~1.0 Mpa for evaporator pressure, 2.1~2.7 Mpa for condenser pressure, 0~10℃ for degree of superheating, and 0~10℃ for degree of subcooling. Finally, a predicted model of COP is proposed for both R410A and R32 systems. According to the response table and ANOVA table, two significant factors contributed to COP are found as evaporator pressure and condenser pressure. Meanwhile, the optimum COP calculated from predicted model has a good agreement with the data of cycle theory. In addition, the value of optimum COP is 1% higher for R32 system through comparison.
机译:本文研究了R410A和R32制冷循环的最佳性能。首先导出性能系数的理论模型。然后,使用田口方法的L_9(3〜4)正交表进行性能分析。在实验设计中,考虑了四个因素和三个层次。每个因素的范围为:蒸发器压力0.8〜1.0 Mpa,冷凝器压力2.1〜2.7 Mpa,过热度0〜10℃,过冷度0〜10℃。最后,针对R410A和R32系统提出了COP的预测模型。根据响应表和ANOVA表,发现影响COP的两个重要因素是蒸发器压力和冷凝器压力。同时,根据预测模型计算出的最优COP与循环理论数据吻合良好。此外,通过比较,R32系统的最佳COP值高1%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号