【24h】

S-transform based pilot protection method for HVDC transmission lines

机译:高压直流输电线路基于S变换的先导保护方法

获取原文

摘要

Traditional traveling wave protection of HVDC line is easily influenced by fault resistance, and the current differential protection as backup protection has disadvantages of slow operation speed and data synchronization, so this paper proposes a pilot protection method for HVDC line based on S transform. Theoretical analysis shows, for a fault occurring on the forward direction of the protection, the polarities of the fault components of voltage and current detected by protection are opposite, but for a backward direction fault, they are the same. According to these characteristics, a new method based on S transform angle differences to identify the fault direction is presented. In addition, for a pole-earth fault in bipolar HVDC systems, the faulted line can be distinguished from the healthy line in terms of ratio differences of S transform transient voltage energies. Simulation results show that the proposed method can effectively identify internal and external faults, the faulted line and lightning disturbance in different fault conditions.
机译:传统的高压直流输电行波保护容易受到故障电阻的影响,电流差动保护作为后备保护存在运行速度慢和数据同步速度慢的缺点,因此提出了一种基于S变换的高压直流输电先导保护方法。理论分析表明,对于在保护正向发生的故障,保护所检测到的电压和电流的故障分量的极性是相反的,但是对于反向故障,它们的极性是相同的。根据这些特征,提出了一种基于S变换角度差识别故障方向的新方法。此外,对于双极HVDC系统中的极地故障,可以根据S变换瞬态电压能量的比率差异将故障线路与健康线路区分开。仿真结果表明,该方法可以有效地识别不同故障条件下的内外部故障,故障线路和雷电干扰。