Coordinated Control of Demagnetizing Method and Inductive SFCL for DFIG Under Symmetrical Faults

机译:对称故障下双馈双馈退磁方法与感应式SFCL的协调控制

获取原文

摘要

According to grid codes, the doubly fed induction generator (DFIG) based wind turbines should remain connected to the grid and generate additional reactive current during grid faults. However, DFIG is very sensitive to grid disturbances. Demagnetizing method can reduce the rotor voltage, but it requires high demagnetizing current under severe faults. Combining inductive superconducting fault current limiter (SFCL), the required amplitude of demagnetizing current can be reduced. Finally, the required reactive power can be output integrated with TVC control. The simulation results of a 1.5-MW DFIG system validate the theoretical analysis and the feasibility of the proposed control strategy.
机译:根据电网法规,基于双馈感应发电机(DFIG)的风力涡轮机应保持与电网的连接,并在电网故障期间产生额外的无功电流。但是,DFIG对电网干扰非常敏感。退磁方法可以降低转子电压,但是在严重故障下需要较高的退磁电流。结合电感式超导故障限流器(SFCL),可以减小所需的退磁电流幅度。最后,所需的无功功率可以与TVC控制集成在一起输出。 1.5 MW DFIG系统的仿真结果验证了理论分析和所提出控制策略的可行性。