In consideration of the Low Voltage Ride Through (LVRT) requirement proposed in grid codes, a LVRT scheme for Doubly Fed Induction Generator (DFIG) based Wind Turbine Generators (WTGs) using a Resistive-type Superconducting Fault Current Limiter (R-SFCL) and two modified control strategy: Reactive Power Control (RPC) and Inductance-Emulating Control (IEC) is proposed in this paper. The installed position, equivalent modelling of R-SFCL and technical principle for improving LVRT capability are described. In addition, the basic principles of RPC and IEC both of which are activated under grid faults are investigated. Finally, the simulations and the performance evaluation are also conducted compared with the single IEC scheme and single RPC-IEC scheme, which demonstrates the effectiveness and superiority of the proposed scheme on enhancing LVRT capability.
机译:考虑到电网规范中提出的低穿越电压(LVRT)要求,采用电阻型超导故障限流器(R-SFCL)的基于双馈感应发电机(DFIG)的风力发电机(WTG)的LVRT方案和本文提出了两种改进的控制策略:无功功率控制(RPC)和电感仿真控制(IEC)。描述了安装位置,R-SFCL的等效模型以及提高LVRT功能的技术原理。此外,还研究了在电网故障下均激活的RPC和IEC的基本原理。最后,与单IEC方案和单RPC-IEC方案进行了仿真和性能评估,证明了该方案在增强LVRT能力方面的有效性和优越性。