首页> 外文会议>Instrumentation, measurement, circuits and systems >Unit Transient Based Protection for High Voltage Wind Power Transmission Lines
【24h】

Unit Transient Based Protection for High Voltage Wind Power Transmission Lines

机译:高压风电线路的暂态保护

获取原文
获取原文并翻译 | 示例

摘要

Based on the wavelet transform results of the transient signals from all ends of the line, a unit protection for high voltage power transmission line is presented. The attenuation effects of high voltage transmission line and busbar capacitance to high-frequency current signals are analyzed. The Transient Current Content Ration(TCCR), Transient Voltage Content Ratio (TVCR) and Transient Voltage Singularity Ratio (TVSR) are deduced according to the analysis of the differences during high frequency voltage transients at each end of the transmission line when in-zone faulted and out-zone faulted. Protection criterion using TCCR and protection criterion using TVSR are proposed, and the principles of protection settings are given. The wavelet modulus maxima of transient signals are used to calculate TCCR and TVSR. Simulation experiments of different faults with EMTP are carried out to test and analyze the protection criteria. A 100kHz sampling rate is used in the simulation experiments. According to the simulation results, the protection criteria prove to be simple, reliable and good for whole line protection.
机译:基于线路两端瞬态信号的小波变换结果,提出了高压输电线路的单元保护方法。分析了高压输电线路和母线电容对高频电流信号的衰减作用。通过分析区域内故障时传输线两端高频电压瞬变期间的差异,推导出瞬态电流含量比(TCCR),瞬态电压含量比(TVCR)和瞬态电压奇异比(TVSR)。和区域故障。提出了使用TCCR的保护准则和使用TVSR的保护准则,并给出了保护设置的原则。瞬态信号的小波模极大值用于计算TCCR和TVSR。利用EMTP对不同故障进行了仿真实验,以测试和分析保护准则。在模拟实验中使用了100kHz的采样率。根据仿真结果,保护标准简单,可靠,对整线保护具有良好的效果。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号